TECHNICAL BULLETIN
Intrusion/Fire/CCTV/Systems
Bosch Security Systems, Inc.
Products
Daylight Saving Time Adjustment October 29, 2007
Issue Severity: Products Affected:
High: Act immediately
Medium: Bosch Security Systems, Inc. strongly
recommends you take the action(s) described
below.
Low: Advisory
Intrusion Products
Fire Products
CCTV Products
Systems Products
1.0 Issue
Starting in 2007, the Daylight Saving Time rules in North America modify so that clocks change on the second Sunday in
March and the first Sunday in November. Prior to 2007, the Daylight Saving Time rules in North America stated that clocks
change on the first Sunday in April and the last Sunday in October.
Also starting in 2007, several Bosch Security Systems, Inc. products will not adjust their internal time on the correct dates
because they will follow the old Daylight Saving Time rules.
Refer to Section
2.0 Resolution for the affected products and the actions you should take to ensure that these products have the
correct time starting on November 4, 2007.
2.0 Resolution
For the products described in the following sections, take the recommended corrective actions before March 11, 2007 to
ensure a smooth transition to the new Daylight Saving Time rules.
For Intrusion products, refer to Section
2.1 Intrusion Products on page 1.
For Fire products, refer to Section 2.2 Fire Products on page 3.
For CCTV products, refer to Section 2.3 CCTV Products on page 3.
For Systems products, refer to Section 2.4 Systems Products on page 4.
For additional information, refer to each product’s installation guide.
2.1 Intrusion Products
2.1.1 GV2 Series/G Series/D7000/D9000 Control Panels (including B-style panels)
These control panels adjust for Daylight Saving Time by using skeds. Modify the sked so that it conforms with the new
Daylight Saving Time rules.
2.1.2 Easy Series Control Panels
Easy Series control panels with v2.5 firmware default to follow the new Daylight Saving Time rules.
For Easy Series control panels with v2.x firmware earlier than v2.5:
If configuring the control panel locally, select Expert Programming Item 121 and change the parameter from 1 (North
America prior to 2007) to 9 (USA after 2006).
If configuring the control panel using RPS, go to System Daylight Saving Time Operation and change the
parameter from North America to North America 2007 and beyond.
For Easy Series control panels in the USA and Canada with v1.x firmware:
Select Expert Programming Item 121 and change the parameter from 1 (North America) to 0 (No time adjustment).
The control panel requires manual time adjustment to follow the new Daylight Saving Time rules.
Przeglądanie stron 0
1 2 3 4 5 6 7 8

Podsumowanie treści

Strona 1 - Products

TECHNICAL BULLETIN Intrusion/Fire/CCTV/Systems Bosch Security Systems, Inc. ProductsDaylight Saving Time Adjustment October 29, 2007 Issue Severity:

Strona 2

2.1.3 Conettix D6600/D6100 Communications Receivers/Gateways For the Conettix D6600 and D6100 Communications Receivers/Gateways, the date and time

Strona 3

Bosch Security Systems, Inc. Products Technical Bulletin TBI 10-19-2007 01 Daylight Saving Time Page 3 © 2007 Bosch Security Systems, Inc.

Strona 4

Bosch Security Systems, Inc. Products Technical Bulletin TBI 10-19-2007 01 Daylight Saving Time Page 4 © 2007 Bosch Security Systems, Inc.

Strona 5

Bosch Security Systems, Inc. Products Technical Bulletin TBI 10-19-2007 01 Daylight Saving Time Page 5 © 2007 Bosch Security Systems, Inc.

Strona 6

Bosch Security Systems, Inc. Products Technical Bulletin TBI 10-19-2007 01 Daylight Saving Time Page 6 © 2007 Bosch Security Systems, Inc.

Strona 7 - Trademarks

Bosch Security Systems, Inc. Products Technical Bulletin TBI 10-19-2007 01 Daylight Saving Time Page 7 © 2007 Bosch Security Systems, Inc.

Strona 8

© 2007 Bosch Security Systems, Inc. 130 Perinton Parkway, Fairport, NY 14450-9199 USA (800) 289-0096 TBI 10-19-2007 01 Daylight Saving Time Technica

Komentarze do niniejszej Instrukcji

Brak uwag