Initial Startup
Parameterization
Timer program
heating circuit 2
520 . . . 536 (same as timer program heating circuit 1)
Timer program
3 / HCP
540 E
Preset value
-
Mon - Sun, Mo - Fri, Sat - Sun, Mon, Tue,
Wed, Thu, Fri, Sat, Sun
Mon - Sun
541 E
1. phase ON
hh:mm 00:00 24:00 06:00
542 E
1. phase OFF
22:00
543 E
2. phase ON
- - . - -
544 E
2. phase OFF
- - . - -
545 E
3. phase ON
- - . - -
546 E
3. phase OFF
- - . - -
556 E
Default values
-
Yes No
No
Timer program
4 / PWH
560 E
Preset value
- Mon - Sun, Mo - Fri, Sat - Sun, Mon, Tue, Wed,
Thu, Fri, Sat, Sun
Mo - So
561 E
1. phase ON
hh:mm 00:00 24:00 00:00
562 E
1. phase OFF
05:00
563 E
2. phase ON
- - . - -
5 64 E
2. phase OFF
- - . - -
565 E
3. phase ON
- - . - -
566 E
3. phase OFF
- - . - -
5 76 E
Default values
-
Yes No
No
Vacation heating
circuit 1
642 E
Vacation period 1 HC1:
First day
dd.mm 1.01 31.12 --.--
643 E
Vacation period 1 HC1:
Last day
dd.mm 1.01 31.12 --.--
648 E
Vacation operating level 1
HC1
-
Frost protection Reduced Frost protection
Vacation heating
circuit 2
652 . . . 658 (same as vacation heating circuit 1)
Vacation heating
P
662 . . . 668 (same as vacation heating circuit 1)
Heating circuit 1 710 E
Comfort setpoint
°C
Value from control
line 716
Value from control
line 713
20
712 E
Reduced setpoint
°C
Value from control
line 714
Value from control
line 710
19
714 E
Frost protection setpoint
° C 4
Value from control
line 712
10
720 E
Slope of the characteristic
- 0.1 4 0.8
730 E
Summer/winter
switching temperature
°C - - - / 8 30 20
740 I
Min. flow setpoint
°C 8
Value from control
line 741
8
741 I
Max. flow setpoint
°C
Value from control
line 741
95 50
850 F
Floor drying function
-
OFF, function heating, ready for covering
heating, function/surface ready, manual
OFF
851 F
Floor setpoint, manual
°C 0 95 25
855 E
Floor setpoint, current
°C 0 95 0
856 E
Floor, current day
- 0 32 0
Control line
Control level
Function
Unit
Min
Max
Factory
settings
F = Function E = End User I = Initial Startup