Technical Data
AQUATOP T12C-T19C
1) without circulating pump
2) measured value averaged around heat pump (free field)
3) residual delivery pressure is indicated at highest level
Heat Pump Type AQUATOP T12C T14C T19C
Electrical Data
Operating voltage, feed 3 x 400 V
Rated input with B0 / W35 PNT kW 2.8 3.3 4.0
Ext. fuse AT 16 20 20
Rated current immersion heater l max. A 10,0 10,0 10,0
Rated current heat pump I max. A 10,0 12,4 14,0
Current with blocked rotor (LRA) LRA A 50 66
Starting current with soft starter VSA A 25 27.5 33.8
Power consumption el. immersion heater max. kW 6/4/2
Power consumption circulating pumps max. kW 0.2 0.3 0.5
Starts per hour max. 3 3 3
Start delay after power outage sec. 60-120
Dimensions / Connections / Misc.
Operating weight kg
Dimensions WxDxH mm 670x960x1050 670x960x1050 670x960x1050
Heating circuit connection IT inch 1" 1" 1"
Brine circuit connection IT inch 1¼" 1¼" "
Sound power level Lwa dB(A) 45 48 51
Sound level at 5-m distance 2) Lpa dB(A) 27 31 34
Expansion vessel heater V l 12 12 2 x 12
Set default pressure heating circuit p bar 1,0 1,0 1,0
Expansion vessel brine circuit V l 12 12 12
Set default pressure brine circuit p bar 0.5 0.5 0.5
Safety valve (brine/heater) p bar 3 3 3
Switching point brine pressure monitor p bar 0.65 0.65 0.65
74